Luminaire Quantity Estimator

Estimate a starting fixture count for indoor general lighting using the lumen method. Enter project-specific assumptions before using the result.

Calculation inputs and results

Enable JavaScript to use the estimator. Fixture count = maintained illuminance (lx) × area (m²) ÷ (luminaire output in lm × room utilance × maintenance factor), rounded up to a whole fixture.

Enter your project data · results update as you type

Changing units converts your entered values.

Use the area of the defined working plane; this tool assumes one open area.

Changing units converts the entered target.

Choose the target for your task and applicable requirements. No standard value is assumed.

Use the complete luminaire’s initial output, not bare-lamp lumens.

Include driver power. Used only for total connected load.

Luminaire-based factor: useful work-plane flux ÷ luminaire output. Obtain it for the room geometry, reflectances and light distribution; do not substitute a lamp-based CU.

Use your maintenance plan and expected depreciation / dirt conditions. This tool supports factors from 0.01 to 1.

Preliminary quantity

—

Complete the area, target, lumens, utilance and maintenance factor to see an estimate.

Estimated maintained average—

Total connected load—

No project assumptions have been applied.

A count estimate does not establish spacing, uniformity, glare, emergency-lighting compliance or hazardous-area suitability. Check the final layout with IES/LDT photometry. Mounting height and surface reflectance must be reflected in the selected utilance; beam footprint alone cannot determine fixture count.

Quantity calculation method & limits

N = ceil(E × A ÷ (Φ × U × MF)). E is maintained average illuminance in lux; A is area in m²; Φ is initial complete-luminaire output in lumens. After rounding up, estimated maintained average = N × Φ × U × MF ÷ A. Connected load = N × input watts.

The IES lumen method estimates average illuminance. Room utilance here is based on luminaire output; lamp-based coefficient of utilization uses a different flux denominator. Keep the factor and lumen basis consistent. The maintenance factor accounts for reduction relative to initial illuminance.

This simplified model is for preliminary indoor general-lighting estimates over one open area. Obstructions, local task lighting, unusual geometry and nonuniform layouts require a photometric model. Utilance depends on the layout, so check it again after selecting the fixture count.

The illustrative example uses 500 m², 300 lx, 20,000 lm, U = 0.60 and MF = 0.80: 15.625 rounds up to 16 luminaires, giving an estimated 307.2 lx. At 150 W each, connected load is 2,400 W. These are demonstration inputs, not recommended targets or TORMIN product data.

Supported ranges: area 0.000001–1,000,000 m²; each dimension 0.000001–1,000,000 m; target 0.000001–1,000,000 lx; output 1–1,000,000,000 lm; input power 0–1,000,000 W; U and MF 0.01–1. Counts above 1,000,000 are outside this tool’s range. Unit conversion uses 1 ft = 0.3048 m and 1 fc = 1 / 0.3048² lx.