Explosion-Proof Lighting & Fixture Quantity Calculator
Calculate required industrial and hazardous-area LED fixture quantities using the lumen method (N = E × A / (Φ × U × MF)), then match certified TORMIN luminaires.
Calculation inputs and results
Enable JavaScript to use the estimator. Fixture count = maintained illuminance (lx) × area (m²) ÷ (luminaire output in lm × room utilance × maintenance factor), rounded up to a whole fixture.
A count estimate does not establish spacing, uniformity, glare, emergency-lighting compliance or hazardous-area suitability. Check the final layout with IES/LDT photometry. Mounting height and surface reflectance must be reflected in the selected utilance; beam footprint alone cannot determine fixture count.
Quantity calculation method & limits
N = ceil(E × A ÷ (Φ × U × MF)). E is maintained average illuminance in lux; A is area in m²; Φ is initial complete-luminaire output in lumens. After rounding up, estimated maintained average = N × Φ × U × MF ÷ A. Connected load = N × input watts.
The IES lumen method estimates average illuminance. Room utilance here is based on luminaire output; lamp-based coefficient of utilization uses a different flux denominator. Keep the factor and lumen basis consistent. The maintenance factor accounts for reduction relative to initial illuminance.
This simplified model is for preliminary indoor general-lighting estimates over one open area. Obstructions, local task lighting, unusual geometry and nonuniform layouts require a photometric model. Utilance depends on the layout, so check it again after selecting the fixture count.
The illustrative example uses 500 m², 300 lx, 20,000 lm, U = 0.60 and MF = 0.80: 15.625 rounds up to 16 luminaires, giving an estimated 307.2 lx. At 150 W each, connected load is 2,400 W. These are demonstration inputs, not recommended targets or TORMIN product data.
Supported ranges: area 0.000001–1,000,000 m²; each dimension 0.000001–1,000,000 m; target 0.000001–1,000,000 lx; output 1–1,000,000,000 lm; input power 0–1,000,000 W; U and MF 0.01–1. Counts above 1,000,000 are outside this tool’s range. Unit conversion uses 1 ft = 0.3048 m and 1 fc = 1 / 0.3048² lx.
Recommended Illuminance Levels & Lumen Method Formula for Hazardous Areas
Use the lumen method formula N = (E × A) ÷ (Φ × UF × MF) for preliminary industrial and explosion-proof lighting layouts, where E is maintained target illuminance (lx), A is floor area (m²), Φ is initial luminaire flux (lm), UF is room utilance (typically 0.50–0.75), and MF is maintenance factor (typically 0.70–0.80 for IP66 sealed LED fixtures).
| Hazardous / Industrial Area | Target Illuminance (lx) | Typical Mounting Height (m) | Recommended Fixture Type |
|---|---|---|---|
| Petrochemical Process Units & Pipe Racks | 100 – 200 lx | 4 – 10 m | ATEX Linear (BC5402A) or Area Light (BC9306) |
| Industrial Spray & Paint Booths | 500 – 750 lx | 3 – 5 m | High-CRI Glare-Controlled Ex Linear / Panel (BC5405) |
| Warehouses & Chemical Storage Halls | 150 – 300 lx | 6 – 12 m | Explosion-Proof High Bay (BC9304 / BC9307) |
| Offshore Decks, Walkways & Stairwells | 50 – 150 lx | 3 – 6 m | Marine-Grade IP66 Linear (BC5401 / BC5402A) |
| Loading Bays, Compressor & Pump Houses | 150 – 300 lx | 5 – 12 m | High-Power Ex Floodlight (BC9102S / BC9700) |
| Pharmaceutical Ex Cleanrooms | 300 – 500 lx | 2.8 – 4.5 m | Flush-Mount Cleanroom Panel (BC5404 / BC5405) |
Featured Certified Explosion-Proof Luminaires & Categories
Explore All Explosion-Proof Lighting, BC9700 High-Power LED (50–200W, ATEX/IECEx/ABS), BC9102S Modular Floodlight (60–300W, 120–277 VAC), BC5407 Anti-Corrosive Linear (9–81W, WF2 IP66), and BC5401 Twin-Tube Linear (ATEX/IECEx/ABS).