ZLQ3140 Emergency Lighting Control Box — product image

ZLQ3140 Emergency Lighting Control Box

An external emergency power box for compatible lighting circuits. Select the battery and output arrangement to match the connected light source.

Input voltage
100–240 VAC
Emergency output
5–25 W by configuration
Ingress protection
IP66
Dimensions
220 × 150 × 75 mm

ZLQ3140 Emergency Lighting Control Box

An external emergency power box for compatible lighting circuits. Select the battery and output arrangement to match the connected light source.

Technical specifications

Technical data

Input voltage100–240 VAC
Ingress protectionIP66
Ambient temperature−25 to +55 °C
Cable diameter4–8 mm / 6–12 mm; other requirements on request
Dimensions220 × 150 × 75 mm
Installation angle360°
Net weight1.5 kg

Emergency output configurations

Lighting loadEmergency outputLight-source voltageDurationBattery
50 W5 W27–54 VDC≥90 min7.4 V
40 W15 / 25 W30–40 VDC≥180 / ≥90 min respectively14.8 V
≤200 W5 / 10 W3–42 VDC≥180 / ≥90 min respectively7.4 V
≤200 W15 / 25 W36 / 54 VDC≥180 / ≥90 min respectively14.8 V

Original catalogue drawings and tables

View the original catalogue pages
ZLQ3140 original catalogue page 64

Product documents

ZLQ3140 · catalogue extract

Original catalogue · PDF pages 64