Die-cast aluminium body
The enclosure uses die-cast aluminium alloy with an electrostatically sprayed surface.
EXPLOSION PROOF ELECTRICAL EQUIPMENT
BXJ5310 is a configurable junction-box family for lighting, power, control and instrumentation connections. Enclosure size, terminal arrangement and cable entries are selected together for the required wiring layout.
The enclosure uses die-cast aluminium alloy with an electrostatically sprayed surface.
Nine enclosure codes provide different terminal capacities, with limits listed by conductor cross-section.
Top, bottom, left and right cable entries can be specified, with per-side capacity depending on the box and thread size.
A silicone-rubber seal and stainless exposed fasteners form part of the enclosure assembly.
Select a listed catalogue reference and add your installation requirements.
Additional installation and specification requirements are confirmed with your quotation.
| Model | Dimensions | Enclosure size | Select |
|---|---|---|---|
| BXJ5310-I | 190 × 132 × 127 mm | I | |
| BXJ5310-II | 190 × 190 × 127 mm | II | |
| BXJ5310-III | 250 × 190 × 127 mm | III | |
| BXJ5310-IV | 250 × 250 × 127 mm | IV | |
| BXJ5310-V | 300 × 200 × 148 mm | V | |
| BXJ5310-VI | 350 × 250 × 148 mm | VI | |
| BXJ5310-VII | 300 × 300 × 148 mm | VII | |
| BXJ5310-VIII | 350 × 350 × 148 mm | VIII | |
| BXJ5310-IX | 400 × 300 × 148 mm | IX |
| Housing material | Die-cast aluminium alloy |
|---|---|
| Ingress protection | IP66 |
| Catalogue ambient-temperature options | −40 °C to +40 / +45 / +55 / +60 / +70 °C, according to selected variant |
| Terminal arrangement | International brand terminal blocks; blue 2.5 mm² terminals for intrinsically safe version |
| Cable-entry direction codes | Top D / bottom X / left L / right R |
| Catalogue application areas | Gas Zones 1 and 2; dust Zones 21 and 22. Select the applicable protection version. |
| Rated voltage | ≤690 V |
|---|---|
| Rated current | ≤630 A |
| Printed gas marking | Ex eb IIC T6 / T5 / T4 Gb |
| Printed dust marking | Ex tb IIIC T80 °C / T95 °C Db |
| Rated voltage | 36 V DC |
|---|---|
| Rated current | ≤5 A |
| Printed gas marking | Ex ia IIC T6 Gb |
| Printed dust marking | Ex tb IIIC T80 °C Db |
| Terminals | Blue intrinsically safe 2.5 mm² terminals |
Original catalogue drawings. Dimensions are in millimetres unless stated otherwise. Open an image to inspect the full-size drawing.
| Enclosure code | Selection-outline W × H × D (mm) | IS terminals 2.5 mm² | Terminals 2.5 mm² | 4 mm² | 6 mm² | 10 mm² | 16 mm² |
|---|---|---|---|---|---|---|---|
| I | 190 × 132 × 127 | 18 | 18 | 16 | — | — | — |
| II | 190 × 190 × 127 | 18 | 18 | 16 | 14 | — | — |
| III | 250 × 190 × 127 | 30 | 30 | 28 | 22 | 18 | — |
| IV | 250 × 250 × 127 | 50 | 50 | 40 | 30 | 18 | 15 |
| V | 300 × 200 × 148 | 36 | 36 | 30 | 26 | 20 | 16 |
| VI | 350 × 250 × 148 | 90 | 90 | 72 | 56 | 50 | 36 |
| VII | 300 × 300 × 148 | 72 | 72 | 60 | 50 | 36 | 30 |
| VIII | 350 × 350 × 148 | 90 | 90 | 72 | 56 | 50 | 36 |
| IX | 400 × 300 × 148 | 100 | 100 | 84 | 74 | 56 | 44 |
| Thread | I | II | III | IV | V | VI | VII | VIII | IX |
|---|---|---|---|---|---|---|---|---|---|
| G⅜″ | 6 | 6 | 10 | 10 | 18 | 21 | 18 | 21 | 27 |
| G½″ | 6 | 6 | 8 | 8 | 12 | 13 | 12 | 13 | 17 |
| G¾″ | 3 | 3 | 5 | 5 | 10 | 12 | 10 | 12 | 14 |
| G1″ | 2 | 2 | 3 | 3 | 6 | 7 | 6 | 7 | 9 |
| G1¼″ | 1 | 1 | 2 | 2 | 3 | 4 | 3 | 4 | 5 |
| G1½″ | 1 | 1 | 2 | 2 | 2 | 3 | 2 | 3 | 4 |
| G2″ | — | — | — | — | 2 | 2 | 2 | 2 | 3 |
| Thread | I | II | III | IV | V | VI | VII | VIII | IX |
|---|---|---|---|---|---|---|---|---|---|
| G⅜″ | 4 | 6 | 6 | 10 | 9 | 10 | 18 | 21 | 18 |
| G½″ | 2 | 6 | 6 | 8 | 6 | 8 | 12 | 13 | 12 |
| G¾″ | 1 | 3 | 3 | 5 | 6 | 5 | 10 | 12 | 10 |
| G1″ | 1 | 2 | 2 | 3 | 3 | 3 | 6 | 7 | 6 |
| G1¼″ | 1 | 1 | 1 | 2 | 2 | 2 | 3 | 4 | 3 |
| G1½″ | — | 1 | 1 | 2 | 1 | 2 | 2 | 3 | 2 |
| G2″ | — | — | — | — | 1 | — | 2 | 2 | 2 |
Original catalogue extract · 5 pages · PDF · 2048 KB
View documentOriginal catalogue pages 1, 2, 3, 4, 5
View document