BXJ5310 is a configurable junction-box family for lighting, power, control and instrumentation connections. Enclosure size, terminal arrangement and cable entries are selected together for the required wiring layout.

Housing material
Die-cast aluminium alloy
Ingress protection
IP66
Voltage by version
Ex e: ≤690 V; Ex i: 36 VDC
Current by version
Ex e: ≤630 A; Ex i: ≤5 A

Terminal connections in an aluminium enclosure

Die-cast aluminium body

The enclosure uses die-cast aluminium alloy with an electrostatically sprayed surface.

Terminal capacity by enclosure

Nine enclosure codes provide different terminal capacities, with limits listed by conductor cross-section.

Entry layout by direction

Top, bottom, left and right cable entries can be specified, with per-side capacity depending on the box and thread size.

Sealing and retained hardware

A silicone-rubber seal and stainless exposed fasteners form part of the enclosure assembly.

Choose your configuration

Select a listed catalogue reference and add your installation requirements.

Additional installation and specification requirements are confirmed with your quotation.

Catalogue configurations

ModelDimensionsEnclosure sizeSelect
BXJ5310-I190 × 132 × 127 mmI
BXJ5310-II190 × 190 × 127 mmII
BXJ5310-III250 × 190 × 127 mmIII
BXJ5310-IV250 × 250 × 127 mmIV
BXJ5310-V300 × 200 × 148 mmV
BXJ5310-VI350 × 250 × 148 mmVI
BXJ5310-VII300 × 300 × 148 mmVII
BXJ5310-VIII350 × 350 × 148 mmVIII
BXJ5310-IX400 × 300 × 148 mmIX

Technical specifications

Common enclosure specifications

Housing materialDie-cast aluminium alloy
Ingress protectionIP66
Catalogue ambient-temperature options−40 °C to +40 / +45 / +55 / +60 / +70 °C, according to selected variant
Terminal arrangementInternational brand terminal blocks; blue 2.5 mm² terminals for intrinsically safe version
Cable-entry direction codesTop D / bottom X / left L / right R
Catalogue application areasGas Zones 1 and 2; dust Zones 21 and 22. Select the applicable protection version.

Increased-safety version — catalogue ratings

Rated voltage≤690 V
Rated current≤630 A
Printed gas markingEx eb IIC T6 / T5 / T4 Gb
Printed dust markingEx tb IIIC T80 °C / T95 °C Db

Intrinsically safe version — catalogue ratings

Rated voltage36 V DC
Rated current≤5 A
Printed gas markingEx ia IIC T6 Gb
Printed dust markingEx tb IIIC T80 °C Db
TerminalsBlue intrinsically safe 2.5 mm² terminals

Dimensions and mounting

Original catalogue drawings. Dimensions are in millimetres unless stated otherwise. Open an image to inspect the full-size drawing.

BXJ5310 original dimension and mounting drawing
Cable entry direction / inlet wiring layout
BXJ5310 original dimension and mounting drawing
Enclosure types I–VI · original dimension drawings
BXJ5310 original dimension and mounting drawing
Enclosure types VII–IX · original dimension drawings

Enclosure selection and maximum fitted terminals

Enclosure selection and maximum fitted terminals
Enclosure codeSelection-outline W × H × D (mm)IS terminals 2.5 mm²Terminals 2.5 mm²4 mm²6 mm²10 mm²16 mm²
I190 × 132 × 127181816———
II190 × 190 × 12718181614——
III250 × 190 × 1273030282218—
IV250 × 250 × 127505040301815
V300 × 200 × 148363630262016
VI350 × 250 × 148909072565036
VII300 × 300 × 148727260503630
VIII350 × 350 × 148909072565036
IX400 × 300 × 14810010084745644

Maximum cable entries per side — Top / bottom (D/X)

Maximum cable entries per side — Top / bottom (D/X)
ThreadIIIIIIIVVVIVIIVIIIIX
G⅜″6610101821182127
G½″66881213121317
G¾″33551012101214
G1″223367679
G1¼″112234345
G1½″112223234
G2″————22223

Maximum cable entries per side — Left / right (L/R)

Maximum cable entries per side — Left / right (L/R)
ThreadIIIIIIIVVVIVIIVIIIIX
G⅜″46610910182118
G½″266868121312
G¾″133565101210
G1″122333676
G1¼″111222343
G1½″—11212232
G2″————1—222

Installation notes

  • D = top, X = bottom, L = left and R = right.
  • Metric or NPT entry requirements must be stated with the order, rather than substituted for a listed G-thread hole.

Ordering notes

  • Specify enclosure code, protection concept, terminal rating and count, and entry direction/thread/count.
  • Entry capacities are the maximum number on one side for the stated thread; the actual layout is selected for the wiring requirements.
  • The selection-outline dimensions and the installation drawing dimensions serve different purposes; use the original mounting drawing for fixing positions.
  • Confirm the exact protection version, temperature class and ambient conditions against the applicable model documents.

Product documents

BXJ5310 · product datasheet

Original catalogue extract · 5 pages · PDF · 2048 KB

View document

BXJ5310 · 2024 TORMIN Explosion Proof Electrical Equipment Catalogue

Original catalogue pages 1, 2, 3, 4, 5

View document

Tell us what you need.

Fields marked * are required.

Your details will be used to respond to this enquiry.