Power Factor and THD in Industrial LED Lighting: How to Compare Test Data

By

Power Factor and THD in Industrial LED Lighting: How to Compare Test Data

Compare LED lighting power factor and THD only after matching the tested assembly, supply, operating point and metric definitions. Then judge the results against the project’s stated criteria. A higher PF means less RMS input current for the same active input power and voltage; a lower current THD means less harmonic current relative to its stated reference. Neither figure alone proves efficiency or compliance.

The useful purchasing question is therefore more specific than “Which driver has the better number?” It is: Which submitted result applies to the offered luminaire in the operating modes this project requires?

PF, THD and efficiency answer different questions

Metric What it describes What it cannot establish by itself
True power factor, PF Active input power divided by apparent input power Driver conversion efficiency, light output or harmonic-current compliance
Current THD, THD-I Harmonic current relative to the report’s reference current Voltage distortion, optical flicker or the full distribution of individual harmonics
Voltage THD, THD-V Harmonic voltage relative to the report’s reference voltage The luminaire’s current THD
Driver efficiency Electrical output power divided by electrical input power PF or the luminaire’s light output per watt

The DOE CALiPER report, “Reported Power Quality Metrics,” pp. 11–12, distinguishes true PF, displacement PF, current THD and voltage THD. Keep those names attached to the numbers when transferring results from a test report to a comparison sheet.

For the separate meanings of watts, lumens and luminaire efficacy, use the industrial lighting specifications reference.

Why true PF can differ from displacement PF

Displacement PF describes the phase relationship between the fundamental-frequency voltage and current. At a 50 Hz supply, that means their 50 Hz components. True PF uses active power and the total RMS voltage and current, so distortion also matters.

A current can be approximately aligned with the voltage at the fundamental frequency while still arriving in narrow pulses. A conventional rectifier followed by a bulk capacitor illustrates why: it can draw charging current during only part of each cycle. Good fundamental alignment therefore does not guarantee a high true PF. Virginia Tech’s Power Factor Correction module, pp. 2–4, develops this distinction and the rectifier example. It explains a mechanism, not the internal design of every LED driver.

For report comparison, “cos φ = 0.98” and “true PF = 0.98” are not interchangeable declarations. Ask which quantity was measured before ranking them.

What a PF improvement changes—and what it does not

For a single-phase AC input:

True PF = P / (Vrms × Irms)
Irms = P / (Vrms × true PF)

Here, P is active input power in watts; apparent power, Vrms × Irms, is in volt-amperes. The relationship follows the Virginia Tech module’s definition, equation (1).

Consider two hypothetical operating cases, each drawing 100 W at 230 V RMS in steady operation:

Assumed true PF Apparent power, P/PF Calculated RMS input current
0.90 111.1 VA 0.483 A
0.98 102.0 VA 0.444 A

The second case requires about 8.2% less RMS current at that same input power and voltage. Both still draw 100 W: the calculation demonstrates a current/apparent-power difference, not an 8.2% reduction in the luminaire’s energy consumption. It provides no information about whether their light outputs are equal.

These are teaching assumptions, not TORMIN measurements. They describe steady-state single-phase input, not inrush or a circuit/protection design.

Separate power factor and THD report records beside a TORMIN ZY8601S luminaire
PF and THD describe different input characteristics. Dashed links associate report records with the luminaire; no measured values or electrical connections are shown.

Read the THD denominator before comparing percentages

Harmonics are components at integer multiples of the fundamental frequency. For current THD referenced to the fundamental, combine the included harmonic RMS currents by root-sum-square, then divide by the fundamental RMS current:

THD-I, fundamental (%) = 100 × √(I2² + I3² + … + IK²) / I1

I1 is the fundamental component; K is the highest included harmonic order. The DOE report, p. 12, describes this basis and explains that another normalization uses total RMS rather than fundamental RMS as the denominator.

To see why the distinction matters, assume a fictional current contains only a 1.00 A RMS fundamental, a 0.30 A third harmonic and a 0.40 A fifth harmonic, with no DC component:

Combined harmonic RMS = √(0.30² + 0.40²) = 0.50 A
Fundamental-referenced THD-I = 0.50 / 1.00 × 100 = 50.0%
Total RMS current = √(1.00² + 0.30² + 0.40²) ≈ 1.118 A
Harmonic RMS / total RMS = 0.50 / 1.118 × 100 ≈ 44.7%

The waveform has not improved: only the denominator changed. That is why a bare “THD 45%” cannot be ranked against “THD 50%” until the reference quantity and harmonic range are known. Nor should harmonic percentages be added arithmetically: this example’s 30% and 40% components combine to 50%, not 70%.

Record THD-I or THD-V, the denominator, included harmonic orders and the measurement method. An input-current distortion figure is also not an optical flicker result; flicker requires evidence about changing light output.

Match the assembly and operating point

Even correctly named metrics can describe different tests. Check these fields before deciding that an electrical result applies to the quotation:

Field A useful comparison establishes Why it changes the decision
Tested object Complete luminaire or separate driver, exact identity and configuration A component result needs a documented link to the offered assembly and load
Supply RMS voltage, frequency and source waveform conditions Results obtained on different supplies do not establish performance at the same project condition
Operating point Connected load and supported full-output/dimmed state A full-output figure does not demonstrate another operating point
Definitions True/displacement PF; THD quantity, denominator and harmonic range Similar labels can conceal different quantities
Method and traceability Report ID/revision, method, measurement bandwidth and uncertainty where relevant Small numerical differences may not support a meaningful ranking

NIST’s 2013 LED power-measurement study identifies measurement bandwidth and source impedance as influences on measured active power in the investigated setup. Its result supports checking the measurement conditions, not applying a universal correction to another lamp.

When the actual project uses dimming, specify the control arrangement and operating points to be assessed. Do not interpret an unspecified “50%” as necessarily meaning half input power or half light output.

Voltage, load and operating-mode report records beside a TORMIN ZY8601S luminaire
Match the tested assembly and conditions before ranking results. The illustration assigns no electrical reading or dimming capability to this model.

Worked comparison: turn the reports into a decision

The following records and project criteria are fictional teaching examples, not TORMIN tests, offers or regulatory limits. Assume the electrical brief requires:

  • Complete-luminaire evidence at 230 V, 50 Hz.
  • True PF at least 0.90 and fundamental-referenced current THD no more than 20% at both full output and a specified dimmed operating point.
  • A separately defined review of any applicable harmonic-current standard.

First submission: distinguish a usable record from a mismatch

Submitted information Offer A Offer B
Tested object Offered complete luminaire and configuration identified Separate driver; link to offered luminaire missing
Supply and mode 230 V, 50 Hz, full output 120 V, 60 Hz; mode unstated
PF True PF 0.95 “PF 0.98”; definition missing
Harmonics THD-I 10%, fundamental basis, orders 2–40 “THD 8%”; basis and range missing
Review outcome Meets the two stated full-output numerical criteria; dimmed result still needed Cannot establish performance at the required condition

Offer A already supports a limited positive conclusion. Offer B’s more attractive numbers do not support a ranking because its test boundary differs. Ask B for matching complete-luminaire evidence, rather than treating its driver headline as proof.

Matching evidence: complete the electrical-metric assessment

Now assume matching reports arrive for both offered assemblies. Their methods, source conditions and fundamental-referenced THD range, orders 2–40, align; the hypothetical report uncertainties do not change the threshold decisions below. Both products support the specified dimmed operating point with their identified control arrangements.

Required operating point Offer A: true PF / THD-I Offer B: true PF / THD-I Decision against the fictional brief
Full output, 230 V / 50 Hz 0.95 / 10% 0.98 / 15% Both meet the stated PF and THD criteria
Specified dimmed point, 230 V / 50 Hz 0.92 / 18% 0.88 / 25% A meets both; B fails both at this operating point

A meets this brief’s PF/THD criteria at both required points; B does not. B’s higher full-output PF does not overcome its dimmed-condition failure. At full output alone, A has lower THD-I while B has higher PF: those are distinct advantages, not a universal winner.

This closes the defined metric comparison. It does not approve A’s entire installation or establish harmonic-standard compliance. Those are separate decisions with their own evidence.

Why low THD alone does not prove compliance

The IEC public description of IEC 61000-3-2:2018+AMD1:2020+AMD2:2024 describes limits on input-current harmonic components for equipment within its scope, tested under specified conditions. It is not a universal “THD below X%” rule for every industrial lighting project.

A single total percentage does not identify how that distortion is distributed between harmonic orders. In the example above, meeting the buyer’s assumed 20% criterion therefore cannot replace the applicable component-by-component assessment.

Identify the applicable edition, equipment classification, jurisdiction and test conditions with the responsible reviewer. Use the corresponding report for that assessment. The public IEC catalogue supports this scope distinction; it does not provide the licensed procedure or establish national adoption.

Record the conclusion, not just the missing documents

Use a comparison record that preserves what is known and what remains open:

Offered model/configuration and tested assembly:
Report ID, revision, method and date:
Supply voltage/frequency/source conditions:
Required operating points and control arrangement:
Active input power, RMS voltage/current and true PF:
THD quantity, denominator and included harmonic range:
Project criterion → reported result → met/not met/not demonstrated:
Applicable harmonic-standard assessment, recorded separately:
Open evidence item, responsible respondent and affected decision:

“Not demonstrated” means the evidence is missing or does not match; “not met” means applicable evidence fails the stated criterion. Keeping these outcomes separate prevents both premature acceptance and unjustified rejection.

For a TORMIN enquiry, send the proposed configuration, supply and operating requirements and request the matching electrical evidence. Compare lifetime declarations separately using the industrial LED lighting lifetime guide.

Sources