Voltage Drop Calculator

Screen conductor resistive drop using a one-way cable length and a balanced supply assumption. This is not cable ampacity, protection coordination or installation approval.

Use line-to-neutral voltage for single-phase and line-to-line voltage for three-phase.

Your screening result

Enter your inputs and select Calculate.

Screening only. This tool does not classify hazardous areas or approve a product, installation or safety system. Use the applicable project requirements, manufacturer data and exact certificate conditions.

Method & limits

Resistance-only screening model: single-phase drop = 2 × L × I × rho / A; three-phase drop = sqrt(3) × L × I × rho / A. Power-mode current = P/(V × PF), or P/(sqrt(3) × V × PF) for balanced three-phase. The output is an I×R drop estimate, not the complete AC phasor voltage-drop calculation: reactance and phase-angle projection are omitted. Resistivity values are nominal 20°C planning constants; hot conductors and actual cable resistance need review. The suggested size is the first listed size meeting the 3% screen, not an approved cable selection.

Frequently asked questions

Is length the round trip?

No. Enter one-way length. The single-phase factor of 2 accounts for the outgoing and return conductors.

Are 3% and 5% universal limits?

No. They are comparison thresholds. Supply origin, circuit purpose, local rules and upstream drop determine the project limit.

Does suggested size include ampacity?

No. Check current capacity, installation method, grouping, temperature, fault protection, terminals and voltage-drop requirements separately.

Why is this only an AC screening estimate?

The model omits reactance and phase-angle projection and assumes balanced three-phase loading. Use cable-manufacturer impedance data for final AC design.

Are the resistance values for hot cables?

No. Copper 0.0175 and aluminium 0.0282 Ω·mm²/m are nominal 20°C assumptions. Resistance generally rises with temperature.

Sources & verification

Source and calculation review: 2026-11-05. Reference methods do not replace the edition adopted for your project.