BXJ8310 Explosion Proof Junction Box — product image

EXPLOSION PROOF ELECTRICAL EQUIPMENT

BXJ8310 Explosion Proof Junction Box

BXJ8310 provides terminal connections for lighting, power, control and instrumentation circuits. The family uses resin enclosures in several sizes, with terminal and entry capacities stated by enclosure code.

Housing material
Unsaturated polyester resin
Ingress protection
IP66
Voltage by version
Ex e: ≤690 V; Ex i: 36 VDC
Current by version
Ex e: ≤630 A; Ex i: ≤5 A

Configurable resin terminal boxes

Polyester-resin enclosure

The body is molded from unsaturated polyester resin.

Labyrinth cover joint

A labyrinth joint and silicone-rubber seal form the cover interface.

Eleven enclosure sizes

The selection table provides eleven enclosure codes, with terminal limits linked to conductor cross-section.

Flexible entry planning

Cable-entry direction, thread and quantity are specified for the project; stainless exposed fasteners use a retained design.

Choose your configuration

Select a listed catalogue reference and add your installation requirements.

Additional installation and specification requirements are confirmed with your quotation.

Catalogue configurations

ModelDimensionsEnclosure sizeSelect
BXJ8310-I150 × 150 × 122 mmI
BXJ8310-II220 × 130 × 120 mmII
BXJ8310-III225 × 150 × 160 mmIII
BXJ8310-IV260 × 180 × 120 mmIV
BXJ8310-V260 × 180 × 160 mmV
BXJ8310-VI360 × 220 × 120 mmVI
BXJ8310-VII360 × 220 × 170 mmVII
BXJ8310-VIII360 × 360 × 120 mmVIII
BXJ8310-IX360 × 360 × 170 mmIX
BXJ8310-X520 × 400 × 220 mmX
BXJ8310-XI720 × 420 × 160 mmXI

Technical specifications

Common enclosure specifications

Housing materialUnsaturated polyester resin
Ingress protectionIP66
Catalogue ambient-temperature options−40 °C to +40 / +45 / +55 / +60 / +70 °C, according to selected variant
Terminal arrangementInternational brand terminal blocks; blue 2.5 mm² terminals for intrinsically safe version
Cable-entry direction codesTop D / bottom X / left L / right R
Catalogue application areasGas Zones 1 and 2; dust Zones 21 and 22. Select the applicable protection version.

Increased-safety version — catalogue ratings

Rated voltage≤690 V
Rated current≤630 A
Printed gas markingEx eb IIC T6 / T5 / T4 Gb
Printed dust markingEx tb IIIC T80 °C / T95 °C Db

Intrinsically safe version — catalogue ratings

Rated voltage36 V DC
Rated current≤5 A
Printed gas markingEx ia IIC T4 Gb
Printed dust markingEx tb IIIC T80 °C Db
TerminalsBlue intrinsically safe 2.5 mm² terminals

Dimensions and mounting

Original catalogue drawings. Dimensions are in millimetres unless stated otherwise. Open an image to inspect the full-size drawing.

BXJ8310 original dimension and mounting drawing
Cable entry direction / inlet wiring layout
BXJ8310 original dimension and mounting drawing
Enclosure types I–VI · original dimension drawings
BXJ8310 original dimension and mounting drawing
Enclosure types VII–XI · original dimension drawings

Enclosure selection and maximum fitted terminals

Enclosure selection and maximum fitted terminals
Enclosure codeSelection-outline W × H × D (mm)IS terminals 2.5 mm²Terminals 2.5 mm²4 mm²6 mm²10 mm²16 mm²
I150 × 150 × 12212121086—
II220 × 130 × 1202828221614—
III225 × 150 × 1602828221614—
IV260 × 180 × 120353528201614
V260 × 180 × 160353528201614
VI360 × 220 × 120505040302520
VII360 × 220 × 170505040302520
VIII360 × 360 × 12010010080605040
IX360 × 360 × 17010010080605040
X520 × 400 × 2201601601301008070
XI720 × 420 × 160240240200150120100

Maximum cable entries per side — Top / bottom (D/X)

Maximum cable entries per side — Top / bottom (D/X)
ThreadIIIIIIIVVVIVIIVIIIIXXXI
G⅜″4812914152315236045
G½″469812121812184139
G¾″244579149143529
G1″124367117112219
G1¼″—24224848129
G1½″———223535107
G2″—————333375
G2½″—————————34
G3″—————————2—

Maximum cable entries per side — Left / right (L/R)

Maximum cable entries per side — Left / right (L/R)
ThreadIIIIIIIVVVIVIIVIIIIXXXI
G⅜″45971091417264530
G½″2466981214213327
G¾″124345811172720
G1″11224467111812
G1¼″—12222448116
G1½″———11233585
G2″—————113363
G2½″—————————23
G3″—————————2—

Installation notes

  • D = top, X = bottom, L = left and R = right.
  • Metric or NPT entry requirements must be stated with the order, rather than substituted for a listed G-thread hole.

Ordering notes

  • Specify enclosure code, protection concept, terminal rating and count, and entry direction/thread/count.
  • Entry capacities are the maximum number on one side for the stated thread; the actual layout is selected for the wiring requirements.
  • The selection-outline dimensions and the installation drawing dimensions serve different purposes; use the original mounting drawing for fixing positions.
  • Confirm the exact protection version, temperature class and ambient conditions against the applicable model documents.

Product documents

BXJ8310 · product datasheet

Original catalogue extract · 6 pages · PDF · 1734 KB

View document

BXJ8310 · 2024 TORMIN Explosion Proof Electrical Equipment Catalogue

Original catalogue pages 6, 7, 8, 9, 10, 11

View document

Tell us what you need.

Fields marked * are required.

Your details will be used to respond to this enquiry.